|
Product
Installation (cont)
Strip Wood/Plank Flooring
Due to expansion and contraction of the boards during seasonal changes,
Floorazzo recommends the use of ¼" or thicker underlayment
panels be installed over these types of floors.
Concrete Floors
Floors shall be smooth, rigid, flat, level, permanently dry, clean and
free of all foreign material such as dust, paint, grease, oils, and
solvents, curing and hardening compounds, sealers, bond breakers, asphalt
and old adhesive residue.
Imperfections such as chips, spalls, cracks and/or corrective leveling
shall be repaired with cementitious-based patching and/or underlayment
materials. Expansion joints in the concrete are designed to allow for
the expansion and contraction of the concrete. If the floor coverings
are installed over the expansion joints, it more than likely will cause
adhesive bond failure and bubbling or buckling of the flooring material.
Therefore, flooring products should not be installed over expansion
joints, and expansion joint covers designed for use with resilient floorings
must be used.
Isolation, construction and control (sawcut) joints may be successfully
patched once the concrete is thoroughly cured, dry and climatized. If
any movement occurs in the concrete it may also cause the patching material
to telegraph.
The surface of the concrete needs to be flat to within 1/8 inch in 10
feet. Flatness to be checked with a string pulled tight over two blocks
of equal height spaced 10 feet apart. If this tolerance is exceeded,
the factory should be called for technical assistance.
It may be difficult to determine if any curing or hardening compounds
and/or sealers have been used. Therefore, an adhesive bond test should
be conducted (and passed) prior to beginning the installation.
Patching Materials
There are many brands available but basically there are two types of
patching materials for the use of smoothing and patching subfloor irregularities.
One type is referred to as calcium sulfate/plaster/gypsum base compounds.
This type of patch may harbor and promote mildew growth, have low indentation
resistance and poor bond and adhesion strength. The use of these compounds
is not recommended.
The second type is a cementitious compound usually with a latex liquid
binder. This type of patch will not promote mildew growth; have much
higher psi strength and better adhesion properties to the subfloor.
Floorazzo recommends only the use of cementitious base patching and
leveling compounds.
Only use the highest quality materials. Many failures have been directly
attributed to the use of gypsum based toppings, leveling and patching
compounds because of poor indentation resistance, poor resistance to
mold and mildew and separation of the product within itself.
Regardless of which patching or leveling compound is used, any failures
in the performance of the compound or Floorazzo tiles due to the compound
is the responsibility of the compound manufacturer, not with Floorazzo.
Old Adhesive Residue
If a residue is asphalitic (cut-back) or other type of adhesive is present,
it must be dealt with in one of two ways:
1. It may be mechanically removed such as: bead blasting or scarifying
2. A self - leveling cementitious underlayment may be applied over it.
Check with the underlayment manufacturer for suitability, application
instructions and warranties.
WARNING!
Warning regarding complete adhesive removal: some solvent based
'cut-back' Asphaltic adhesives may contain asbestos fibers that are
not readily identifiable. Do not use power devices, which create asbestos
dust in removing these adhesives. The inhalation of asbestos dust
may cause asbestosis or other serious bodily harm. Smoking greatly
increases the risk of serious bodily harm.
Never use solvents or citrus adhesive removers to remove old adhesive
residue. Residue left within the subfloor will affect the new adhesive
and the new floor covering. Conducting a pH test and bond test prior
to the installation may help identify the use of these materials.
Existing Resilient Floors
Floorazzo tiles should not be installed over existing resilient floors.
Note: The responsibility of determining if the existing flooring
or subfloor is suitable to be installed over rests solely with the installer
and flooring contractor. Installations over existing resilient flooring
may be more susceptible to indentation, and there is always a possibility
the existing flooring may telegraph through. Remember, you are no better
than what you go over.
Poured Floors
(Epoxy, Polymeric, Seamless)
Floorazzo tiles may be installed over most poured floors provided they
meet the following conditions:
1. Concrete floors that are on, above and below grade - one calcium
chloride moisture test (minimum of three) or ASTM F2170, In-Situ Relative
Humidity of the Concrete. should be conducted for every 1000 sq. ft.
of flooring. The test results should not exceed 3 pounds per 1000 square
feet per 24 hours for the calcium chloride test and 75% for the insitu
relative humidity. The existing flooring and adhesive must be removed
where the test is conducted. (ASTM 1869-04)
2. It must be totally cured and well bonded to the concrete. It must
be free of any residual solvents and petroleum derivatives.
3. Loose, damaged areas and irregularities must be repaired with a cementitious
based patching compound.
4. The texture must be smooth. Sand or wet stone the surface to remove
any grit and texture.
5. All waxes and finishes must be removed and rinsed with clean water
and a pH test should be conducted to assure stripper residues have been
removed.
6. After area has been properly prepared, adhesive bond tests must be
conducted (and passed) with the flooring and adhesive that will be used
on the job. Remember, the weakest link should always be the adhesive.
The responsibility of determining if the existing flooring is suitable
to be installed over rests solely with the installer and the flooring
contractor.
WARNING!
Do not sand, dry sweep, dry scrape, saw, beadblast or mechanically
chip or pulverize existing resilient flooring, backing, lining felt
or asphaltic 'cut-back' adhesives. These products may contain either
asbestos fibers or crystalline silica. Avoid creating dust. Inhalation
of such dust is a cancer and respiratory tract hazard. Smoking by
individuals exposed to asbestos fibers greatly increases the risk
of serious bodily harm. Unless positively certain that the product
is a non-asbestos containing material, you must presume it contains
asbestos. Regulations may require that the material be tested to determine
asbestos content. The RFCI'S Recommended work practices for removal
of resilient floor coverings are a defined set of instructions which
should be followed if you must remove existing resilient floor covering
structures.
Radiant Heated Floors
Floorazzo tile may be installed over radiant heated floors provided
the operating temperature does not exceed 85°F. To allow proper
adhesion of the adhesive to the subfloor, the radiant heating system
should be lowered, or turned off for at least 48 hours prior to installation
of the flooring material. The room temperature must be maintained at
a minimum of 65°F prior to, during and after installation for 72
hours after which the temperature of the radiant heating system can
be increased. When raising the floor temperature, do so gradually so
that the substrate and the flooring material can adapt to the temperature
change together. A rapid change could result in bonding problems. For
more information, contact Floorazzo Technical Services.
Porous and Non-Porous surface
Adhesive Bond Test -
In several locations throughout the area to receive the flooring, glue
down 2'x2' pieces of tile with the recommended adhesive. Bond tests
give the installer the opportunity to evaluate the porosity of the subfloor
and determine the correct timing for application of the flooring material.
The floor should be smooth, dry and allowed to set for 72 hours before
attempting to remove. It is also a good practice to place your bond
test over some areas where a patching compound has been used in order
to check the bond strength of the patching compound. When removing the
test floor check for looseness around the edges of the material, moisture
always takes the path of least resistance. A proper bond test should
show no signs of moisture and it will restrict all movement of the material.
When pulling up the tile you should see proper transfer of adhesive
between the subfloor, and the tile.
On porous subfloors, primers can improve bond strength. They eliminate
moisture from the adhesive being absorbed too fast and improve working
time. Check with the manufacturer of these products for proper application
guidelines and warranties.
Non-porous substrates such as metal, terrazzo, ceramic tile, or marble
can be installed over. However, the same guidelines as mentioned for
installing over concrete or existing floor coverings should be followed.
A bond test is essential!
Note: Remember the weakest link should always be the adhesive.
Even if is takes sufficient force to remove the test flooring but all,
or the majority of the adhesive is adhered to the back of the tile,
the bond is considered unacceptable.
Moisture Testing -
It is essential that moisture tests be taken on all concrete
floors regardless of age or grade level with a minimum of three tests
for the first 1000 square feet. The test should be conducted according
to ASTM F1869-04, Calcium Chloride Moisture Emission Test, or ASTM F2170,
In-Situ Relative Humidity of the Concrete. One test should be conducted
for every 1000 square feet of flooring. The test should be conducted
around the perimeter of the room, near columns and where moisture may
be evident. The results of F1869 Calcium Chloride moisture vapor emissions
from the concrete shall not exceed 3.0 lbs. per 1000 sq. ft. in 24 hrs.
for all tile installations. For the most accurate results, the weight
of the calcium chloride dish should be made on the job site at the start
and end of each test. The results of F2170 In-Situ Relative Humidity
shall not exceed 75%. A diagram of the area showing the location and
results of each test should be submitted to the architect, general contractor
or end user. If the test results exceed the limitations, the installation
should not proceed until the problem has been corrected.
Note: It may not be the floor installer's responsibility to conduct
the test. It is, however, the floor covering installer's responsibility
to make sure these tests have been conducted and that the results are
acceptable prior to installing the floor covering. When moisture
tests are conducted it indicates the conditions only at the time of
the test. The flooring contractor cannot be held responsible if moisture
appears in the future, causing a failure.
pH Testing -
It is essential that pH tests be taken on all concrete floors regardless
of the age or grade level. During the curing process of concrete or
when moisture is present and working its way through the concrete, it
dissolves alkali salts that are contained in the concrete. When the
moisture reaches the surface of the concrete it evaporates, leaving
behind alkali salt residue on the surface. In the presence of moisture
these alkali salts can and will cause several installation and material
problems, such as adhesive failure, discoloration, and shrinkage and
softening of the floor covering. Therefore, pH tests should be conducted
in several locations throughout the area. If moisture tests are at acceptable
levels but the pH tests exceed 9, then a light sanding of the concrete
surface and vacuuming up the residue will usually resolve the problem.
Retest to assure the pH has been neutralized.
TILE INSTALLATION
General
- Ensure that moisture tests have been conducted and that the results
do not exceed 3.0 lbs. per 1000 sq. ft. in 24 hours as per ASTM F-1869-04,
or 75% In-Situ relative humidity when tested according to ASTM F-2170.
- pH of concrete subfloor is not greater than 9.
- A bond test is conducted and passed
- The permanent HVAC system is turned on and set to a minimum of 68°
F (20° C) for a minimum of 72 hours prior to, during and after installation.
After the installations, the maximum temperature should not exceed 100°
F.
- Flooring material has been climatized to the installation area for
a minimum of 24 hours prior to installation. It is possible to crack
the tile during routine handling if they have not been climatized as
recommended. The bulk-shipping container should be broken down into
a series of piles, no more then 3 inches high, scattered around the
room with care for warming.
- The moisture test result determines the recommended adhesive. The
following are our recommendations: 0-3 lbs. Mapei ECO 350, 3-5 lbs.
W. F. Taylor 2091. However, if other adhesives are desired, they can
be used without voiding the warranty by obtaining a letter of authorization
from Floorazzo.
- Use a 1/16" x 1/16" x 1/16" notch trowel only.
- Material should always be visually inspected prior to installation.
Any material installed with visual defects will not be considered a
legitimate claim.
- Ensure that all recommendations for subfloor and jobsite conditions
are met prior to beginning the installation. Once the installation is
started, you have accepted those conditions.
Layout and Installation
IMPORTANT: Because Floorazzo tile is a natural product and
each tile is individually cast, which makes it unique to itself, it
is highly recommended to dry lay the floor prior to installation.
This process will ensure that the visual properties will flow smoothly
from one tile to the next. The installer should dry lay at least 25
tile, step back and review the "look" of the installation
before proceeding.
Floorazzo tile is installed using conventional tile installation techniques.
It is customary to start from the center of the room. In corridors and
small spaces, it may be simpler to work lengthwise from one end, using
the center line as a guide.
The center line is drawn as follows: a chalk line is snapped from
center of wall A - B (=E) to the center of wall C - D (=F). The center
of line E - F is found (M). Draw a perpendicular line through M using
the 3:4:5 method to establish G - H
Starting at center point M, measure out lengthwise and widthwise to
the walls to make sure you will have at least a half of a tile at the
border. Adjust lines E - F and G - H, if necessary.
Adhesive
1. Use adhesive and a 1/16" x 1/16" x 1/16" notch trowel.
Follow the directions on the adhesive label.
2. In most cases, the tile should be placed immediately into the adhesive,
before the adhesive has had an opportunity to dry. Good transfer of
adhesive to the backing of the tile is essential for proper bond. The
installer must understand, however, that subfloor porosity and room
environment (temperature, humidity, air circulation, etc.) may affect
the working characteristics of the adhesive (open time and working time).
When installing over non-porous substrates a short open time may be
appropriate, but under no circumstances should the adhesive be allowed
to dry before placing the tile into the adhesive.
3. Immediately after placing the material into the adhesive, roll in
both directions with a minimum 100 lb roller.
Installation process
1. Begin laying tile at the center point, ensuring that the tile is
laid exactly on the chalk lines. If the first few tiles are not installed
correctly, it will affect the entire installation.
2. Because tile must be installed into wet adhesive, do not spread adhesive
in an area larger than tile can be installed while the adhesive is still
wet.
3. Since it takes time to mark and cut the border tiles, it is advisable
to spread adhesive first only where full tiles will be laid. When the
field is complete, mark and cut the border tiles before the adhesive
is spread. The preferred method for cutting Floorazzo tile is by way
of a wet saw. However, other standard cutting techniques can be used,
at the discretion of the installer. When fitting is complete, adhesive
can be spread in the border area and border pieces can be installed
and rolled while the adhesive is still wet.
Wall Base
Cut tile to desired height and length or install Floorazzo precut
beveled wall base.
Use adhesive and a 1/16" x 1/16" x 1/16" square notch
trowel.
Spread adhesive on the wall and on the back of the tile. Let adhesive
flash off until tacky.
Place tile base onto wall and roll with a hand roller.
|